H2S Removal Methods in Biogas

H2S is one of the worst enemies of biogas engines and pipelines. The removal method is chosen according to the H2S content of the gas, the flow rate and the operating cost.

Why is H2S a problem?

Hydrogen sulfide (H2S) in biogas combines with water and, after combustion, turns into sulfur acids. The result is degraded engine oil, corrosion in heat exchangers and exhaust lines, and maintenance cost. The H2S content of the gas can vary from hundreds to thousands of ppm depending on the feedstock.

Gas engine manufacturers usually state the maximum H2S value allowed at the inlet in their own specification. The target value is set according to this specification and the warranty conditions.

Common methods

  • Air/oxygen dosing in the digester: a small, controlled amount of air is supplied to the gas space and bacteria oxidize H2S to elemental sulfur. It is simple and cheap, but the air quantity must be controlled (dilution of the gas and safety).
  • Iron salt dosing (FeCl2, FeCl3, etc.) in the digester: H2S is bound in the liquid phase. It is effective if the feedstock has a high sulfur content; chemical consumption is continuous.
  • Biological scrubber: bacteria living on a packed bed remove H2S with the help of circulation water. At high H2S values (for example 2000 ppm and above) it protects the life of the following filter.
  • Packed-bed filter (iron oxide/hydroxide based): the gas passes through the bed and H2S is bound. It is common as a final stage or for medium H2S levels; the media is replaced or regenerated when saturated.
  • Activated carbon: used for fine polishing at low H2S values; its capacity is limited by the weight of the fill.

Selection criteria

  • Inlet H2S value and its fluctuation
  • Gas flow rate and target outlet value
  • Media replacement cost and waste management
  • Space, energy and operating staff available
  • Whether air mixing into the gas is acceptable

From the mechanical design side

In filter and tank design, gas velocity, contact time, bed height and gas distribution are decisive. The cover and discharge arrangement for changing the media must be planned from the start; condensate drain and freeze protection must not be forgotten. Because of the corrosive environment, the choice of material and internal coating is also part of the design.

In wide beds where flow distribution is critical, CFD can reveal the risk of short-circuiting (channeling) in advance.